Power Requirement
|
|
120 VAC; 50-60 Hz + 10, -20 VAC 4 VA plus total VA of all devices staged, i.e. contactor coil V.A.
|
|
|
Output Capability
|
|
One Amp per step continuous ten Amps per step inrush.
|
|
|
Signal Output: (Terminals A-B)
|
|
MA AC or MA DC; 4-20 MA standard or 0-5 VAC or VDC. 60 MA and 9V maximum input
|
|
|
Signal Input: (Terminal C-D-E)
|
|
135 Ohm slide wire or potentiometer. 100 Ohms to 1000 Ohms acceptable
|
|
|
Signal Isolation
|
|
1500 Volts from power and ground
|
|
|
Time Delay
|
|
Approximately 10 seconds initial and 10 seconds per step. Automatic 10 seconds per step. Automatic slow down near balance.
|
|
|
Cycling
|
|
Adjustable from differential to time Proportioning.
|
|
|
Ambient Temperature
|
|
30 to 130 ºF
|
|
|
Size
|
|
13-1/2 x 6 x 3-1/2 in
|
|
|
Weight
|
|
3 lb
|
|
Mode of Operation
|
|
Circular Up-Down
|
|
|
Input1
|
|
0-135 Ohms 4-20 mA
|
|
|
Cool Steps
|
|
1 2 3 4 5 6 7 8 9 10
|
|
|
Heat Steps
|
|
1 2 3 4 5 6 7 8 9 10
|
|
1 Other inputs, delays and options available, consult factory.
|
|